|
1.
CONTRACT
DOCUMENTS
- The Contract includes
the SCOPE OF WORK and the
STANDARD GENERAL CONDITIONS of
the Contract.
- The intent of these
documents is to include all
labor, materials, equipment and
services of every kind necessary
for the proper execution of the
work and the terms and conditions
of payment.
- The terms and conditions
of this bid will become the terms
and conditions of the contract
upon acceptance of the bid, and
in case of conflicts will take
precedence. However, no general
specifications herein will be
applicable to any contract unless
such specifications are
specifically identified in the
contract.
2.
SCOPE OF WORK
- Work required under this
section consists of providing all
labor, equipment, materials and
supervision necessary to perform
HVAC remediation, Quality Control
Assurance (QCA) protocols
designed herein and the
techniques specifically required
for the removal of agents
potentially deleterious to human
health, removal of visible
surface contaminants and the
cleaning of air-side surfaces of
all air intakes, air handlers,
coils, dampers, terminal units,
diffusers and duct systems, as
specified herein, including but
not limited to, all adjunct
components in strict accordance
with these specifications.
3.
STANDARD
GENERAL CONDITIONS
- All decontamination
procedures shall be accomplished
by an indoor environmental
company whose personnel have
specialized knowledge and
expertise in the methods required
for the removal and disposal of
visible surface contaminants,
agents potentially deleterious to
human health, and bulk materials
which have been contaminated by
such agents.
- Organization will have
at least one (1) "Certified
Air Duct Cleaning
Specialist" on staff who has
passed the National Air Duct
Cleaners Association
Certification exam and is
verifiable with their current
status.
- Provide Owner with a
proactive IAQ Quality Control
Assurance (QCA) program to assure
remediation work is performed by
a disciplined standard. The
Contractor is to provide a
designated person who has the
training and has been given the
responsibility to take necessary
measures to assure compliance
with OSHA's proposed 1910.1033
Indoor Air Quality Program.
- Occupational Health and
Safety Administration (OSHA)
standards must be complied with.
These include, but may not be
limited to the Personal
Protection Program (PPP), the
Respiratory Protection Program
(RPP) 1910.134, the Confined
Space Program (CSP) 1910.146, and
the Hazard Communications Program
(HCP) 1910.1200. These programs
must be established. The
Contractor also shall provide all
necessary training and equipment
required by the programs for
their personnel.
- The Contractor shall
assure that its employees have
received safety equipment
training, medical surveillance
programs, individual health
protection measures, and
manufacturer's product and
material safety data sheets
(MSDS) required for the work
described by this Contract
Document.
- The Contractor shall
maintain a copy of all current
MSDS documentation and safety
certifications at the site at all
times, as well as comply with all
other site documentation
requirements of the OSHA programs
and this specification.
- All cleaning procedures
shall be accomplished by an
indoor environmental company with
personnel that have specialized
knowledge and expertise in the
methods required for the removal
of such materials.
- Occupational Health and
Safety Administration (OSHA)
general industry standard for
respiratory protection 29 CFR
1910.134 requires that a
respiratory protection program be
established. In order to perform
remediation, employee
certification and an in-house
Respiratory Protection Program
(RPP) documentation must be
submitted.
- The Contractor shall
assure that its employees have
received the necessary training,
medical surveillance programs,
safety equipment, individual
health protection measures, and
manufacturer's product and
material safety data sheets
required for the work described
by this Contract Document 3.10.
The term "antimicrobial
coating product" used in the
following specifications refers
to an antimicrobial formulation
developed, tested and registered
for HVAC ductwork and air handler
applications. The antimicrobial
coating product shall be an EPA
registered, non-toxic, water
soluble solution with supporting
efficacy and MSDS data.
Application of the antimicrobial
coating products shall be in
accordance with manufacturer's
minimum millage surface
application rate standards for
effectiveness.
- List of personnel and
their experience and projects
performed.
- Bids shall be considered
only from firms which are
regularly engaged in the
environmental business with
emphasis on HVAC decontamination
and/or ductwork remediation.
4.
PERFORMANCE
OF WORK - BASELINE CONDITIONS QCA
- Pre and Post-remediation
IAQ QCA
- QCA shall be limited to
the areas specified herein, and
the specific zone/air handling
system to be remediated. No other
areas shall be monitored or other
tests conducted without the
authorization of the Owner.
- Personnel performing
bulk (surface) QCA must be
trained in IAQ. All cultures
shall be quantified and qualified
for microbial content in a
laboratory with a minimum staff
of a Ph.D. in
Mycology/Microbiology Laboratory
.
- QCA of the existing HVAC
parameters shall be done in each
zone/air handling unit system
area prior to any remediation
work in that area.
Testing
shall include: (minimum):
| Test
protocol |
Indoor
(Before)
(Occupied Space) |
Indoor
(After)
(Occupied Space) |
Outdoor
Sample |
| Temperatures
Drybulb (Pre/Post Coil) |
X |
X |
X |
| Temperatures
Wetbulb |
X |
X |
X |
| Relative
Humidity (Pre/Post Coil) |
X |
X |
X |
| Bulk Sample
Microbial Analysis |
X |
X |
- |
| NADCA Vacuum
Test ( Nuisance Dust Protocol) |
X |
X |
- |
| Videographic
Imaging and Still Photos |
X |
X |
- |
| Air Flow
Differential Manometer |
X |
X |
- |
- Contractor
must be capable of conducting
IAQ/HVAC video imaging and still
photos to be provided both before
and after mechanical remediation.
Both the 'before' video tape and
still photos shall be available
to the Owner before remediation.
IAQ/HVAC imaging is to be
completed utilizing VHS video
capabilities before and after
remediation. Optionally, a
narrated and edited tape will be
provided to the Owner.
- Microbiological bulk
sampling, when performed, shall
follow nationally recognized
chain of custody protocols for
data gathering. Culture shall be
performed to identify bacteria
and fungi on appropriate media.
- Cultures are to be
characterized to quantify and
qualify microbial content.
Microbiological evaluations shall
include fungal and bacterial
cultures.
- Initial air flow and
differential pressure readings
are to be performed by the
Contractor using manometer
equipment. Pressure differentials
shall be measured across each
coil, with filtration in place.
- Verification of Air
Conveyance Systems (ACS)
decontamination will be
determined by the NADCA vacuum
test. The weight of the debris
collected by the nuisance duct
protocol shall not exceed
1.0mg/100 cm².
- Provide Owner with QCA
Report, including: VHS video,
photographs and report of
degraded areas of HVAC system,
Microbial results, and air flow
and pressure differential
results.
- All QCA requirements and
procedures shall be completed for
post-remediation quality analysis
in accordance with the post
remediation table provided in
this document.
- In addition, the
following will be required to
complete the post-remediation
QCA:
- Provide Owner
with a QCA Report
including: Remediation
Progress Report summary,
a compilation of daily
progress reports of work
performed, all
correspondence during
remediation of work
performed, HVAC parameter
study, bulk analysis,
IAQ/HVAC video imaging,
differential pressure
readings, NADCA vacuum
test results, wet and dry
thickness (millage)
analysis of antimicrobial
coating applications, and
documentation of any
deficiencies.
- Provide Owner
with records of
compliance after the
completion of the
remediation project. This
QCA analysis is to be
provided to the Owner for
verification of the
Contractors ability to
meet performance criteria
as defined by sections
6.1 to 6.3.1 of NADCA
standard 1992-01 or
current version.
5.
CORRECTION
OF WORK
- The Contractor shall
re-execute any work that fails to
conform to or meet requirements
of the Contract, and which
appears during the progress of
the project, and shall remedy any
defects due to faulty materials
or workmanship which appear
within a period of one year from
the date of final acceptance of
the work by the Owner. The
provisions of this article apply
to work completed by
subcontractors as well as to work
completed by employees of the
Contractor.
6.
QUALITY
ASSURANCE/ QUALIFICATIONS OF BIDDER
- NADCA Standard 1992-01
must be followed with no
modifications or deviations being
allowed to provide the maximum
safety for the occupants in the
building.
- The Contractor selected
should have at a minimum three
years membership with the
National Air Duct Cleaners
Association (NADCA) and be able
to verify three cleaning projects
in which the NADCA standards have
been used.
- All cleaning procedures
shall be accomplished by an
indoor environmental company with
personnel specializing in HVAC
systems. Contractor shall have
knowledge and expertise in the
methods required for the removal
of microbiological contaminants
from within an HVAC system.
Qualified Contractor shall be
capable of performing mechanical,
electrical, plumbing and control
work as necessary to accomplish
this scope of work. Contractor is
required to be state licensed.
- Contractor stipulates
that their work performance has
been in accordance with
specifications and general
techniques in regard to HEPA
vacuums and the application of
antimicrobial products to duct
systems.
- Contractor must have a
minimum of five years experience
in commercial ductwork
decontamination. Additionally,
the Contractor must have
experience with air sampling
techniques as outlined in this
Scope of Work on a minimum
facility of 75,000 square feet.
This project must have been
cleaned with a 4,000 to 6,000 +
CFM HEPA vacuum and an
application of an antimicrobial
coating product to the duct
system.
- List and give a brief
description of similar work
completed with locations, names,
phone numbers and address of
each.
- Bids shall be considered
only from firms which are
regularly engaged in HVAC
maintenance and in the
environmental business with
emphasis on air duct
decontamination.
7.
WORK SCHEDULE
- Unless otherwise
specified, this job is specified
for 1st or 2nd shift work.
- All office equipment and
furniture shall be covered and
protected from any dust or debris
in each work area.
- All systems shall be
back on line and operating at
full capacity, and all areas will
be ready for occupancy no later
than the time agreed upon with
the facilities manager.
- Schedules and progress
reports shall be faxed or
delivered on a daily basis.
8.
MATERIALS,
EQUIPMENT AND PERSONNEL
- Except as otherwise
noted, the Contractor shall
provide and pay for all
materials, labor, tools, and
equipment necessary to complete
the work.
- The Contractor shall
furnish, for approval, all
samples as directed. The work
shall be in accordance with
approved industry sampling
protocols.
- All material shall be
new, and both workmanship and
materials shall be of a high
standard of quality, approved by
the Owner's Representative.
- All workmen and
subcontractors shall be skilled
in their trades.
9.
REQUIREMENTS
FOR SPECIFIC MODIFICATIONS OF CLEANING
AND DECONTAMINATION OF AIR HANDLERS &
ZONE DAMPERS
- The Contractor shall
clean all types of air conveyance
systems (i.e., sheet metal ducts,
masonry, etc.) so that mold,
mildew, lint, hair, fungi, dirt
and other foreign materials and
residues are properly removed.
- The cleaning procedures
shall be accomplished by the
utilization of specialized
equipment as required (i.e., high
suction vacuums utilizing HEPA
filters, high pressure washers,
air compressors, duct brushes,
etc.). (SEE EQUIPMENT
SPECIFICATIONS)
- Special attention shall
be taken during cleaning to
prevent high levels of
micro-organisms from becoming
airborne and then disseminated
into occupied areas. All
effluents shall be removed and
disposed of by the Contractor.
Cleaning shall be in accordance
with NADCA Standard 1992-01.
- Contractor shall, during
decontamination, maintain
certified respirators, safety
glasses and clothing according to
OSHA respiratory protection
standard 29-CFR-1910.134.
10.
ROYALTIES
AND PATENTS
- The Contractor shall pay
all royalties and patent fees for
any material or processes which
require the use of proprietary
patented systems and/or methods.
The Contractor also agrees to
hold the Owner harmless of all
such claims if such issues of
intellectual property arise.
11.
PROTECTION
OF WORK, PROPERTY AND PERSONS
- The Contractor shall
adequately protect the Owner's
property and occupants. The
Contractor shall be responsible
for the cost arising out of any
damage or injury due to his act
or neglect.
12.
ACCESS TO WORK
- The Contractor shall
permit and facilitate observation
of the work by the Owner and his
agents and public authorities at
all times.
13.
CHANGES IN
THE WORK
- The Owner may order
changes in the work, the Contract
Sum being adjusted accordingly.
All such orders and adjustments
shall be in writing. Claims by
the Contractor for extra cost
must be supported by accurate
cost breakdowns, and must be
approved by the Owner before
executing the IAQ work involved.
- Any changes to the
original work order contract will
be executed as agreed upon
utilizing labor and material
rates. These IAQ remediation
personnel rates will apply to any
changes to the scope of the work
order.
- Provide all receipts to
the Owner and Architects for
change orders, as requested.
14.
PLAN
ERRORS, OMISSIONS, AND SPECIFICATION
MODIFICATIONS
- Claims of Plan and/or
Specification errors by the
Contractor for extra cost must be
supported by subject documents in
error, field inspection and
accurate breakdowns, and approved
by the Owner before Contractor
will continue with the contract
work. Consequently, the Owner may
order changes in the work, the
Contract Sum being adjusted
accordingly. All such orders and
adjustments shall be in writing.
All procedures from this point
shall be handled as normal change
orders.
15.
CONTRACTOR
RESPONSIBILITIES
- CONTRACTOR IS NOT
RESPONSIBLE FOR PROBLEMS
RESULTING FROM PRIOR
INAPPROPRIATE OR CARELESS
CLEANING TECHNIQUES OF OTHERS
- Insure that any air
conveyance systems' interior
acoustical lining materials
receive careful attention to
prevent damage to airside
surfaces. Any acoustical or
insulating liner, interior or
exterior that is cut, tooled or
damaged during any procedures
shall be repaired in accordance
with industry specifications.
- Reports will be made of
all motor damage, deteriorating
ductwork and insulation to the
Owner for inspection and decision
as to remedies needed. Most
repairs shall be made upon
discovery to maintain progress.
16.
AIR HANDLERS
- The Contractor shall
insure that the supply and return
fans/blowers relating to these
air handler zones of influence
are thoroughly cleaned. Areas to
be cleaned shall include blowers,
fan housing, blades, vanes,
shafts, baffles, and drive
assemblies. All mechanical or
machined components shall be
maintained for corrosion by
removing loose rust and scale.
Protection of all HVAC parts and
material shall be considered
prior to applying any coating or
treatment. All vanes, shafts,
baffles, drive assemblies or any
other moveable parts within the
air handler shall be properly
lubricated prior to closing and
completing.
- All visual surface
contamination deposits shall be
removed according to NADCA
Standard 1992-01.
- All items within the air
handler units that are sensitive
to, or could be damaged by the
cleaning process, shall be
properly protected during the
work.
- Contractor shall be
equipped and staffed with
qualified personnel capable of
removing electric heat strips,
and any mechanical or plumbing
components required to access
coils.
- Coil access is made by
removing panels of the HVAC
system, opening existing duct
accesses, creating new duct
accesses, installing doors in the
HVAC system panels or complete
removal of the cooling coils. All
coil accesses shall be installed
before and after each coil where
applicable (SMACNA
specification). These are
intended for future maintenance
accesses and shall be as
specified.
- Non toxic, non acid
based coil cleaner will also be
utilized as a cleaning method for
coils.
- The Contractor shall
remove contaminants from all
cooling coils. Coils shall be
thoroughly cleaned on both
exterior surfaces and in the
interior coil bank, all non-
impacted contaminants shall be
removed so the air flow and heat
transfer is not inhibited.
Back-to-back coils must be
removed to accomplish cleaning of
exterior surfaces. No damage to
the coil or fans shall be
incurred. Coils shall be
thoroughly rinsed with clean
water to remove any latent
residues. Coils shall be covered
and protected to prevent heat
transfer reduction created by
overspray of any coatings.
17.
DUCTS
- ACCESS OPENINGS OPTIONS
- The Contractor shall
provide and install access
openings in the ducts and air
handlers as required for proper
cleaning at various points of the
duct system for physical and
mechanical entry. The openings
shall be provided at various
points and adjacent to the
in-line components (i.e. turning
vanes, dampers, etc.) that tend
to entrap contaminants.
- When already installed
in the HVAC system, the
Contractor shall utilize the
existing access openings for
remediation where possible.
- The opening shall be
furnished and installed by the
Contractor.
- Sheet Metal Plate
Option:
- Access openings
shall be resealed with
matching gauge galvanized
plates with outside frame
sealed and screwed to the
ductwork. Patches will have
an application of mastic by
an approved UL listed product
and shall be used in
accordance with SMACNA
standards.
- Sheet Metal Door Option:
- The door shall be
eighteen (18) gauge metal
with 1/2-inch insulation on
the inside. Door edges shall
be twice turned in 1/2-inch
over the insulation. They
will have a hand-type latch
designed to tightly secure
them and prevent air leakage
yet permit re-access at
future times. Doors shall be
marked for easy
identification.
- Rigid Fiberglass
Ductboard Panel Option:
- Rigid fiberglass
ductboard duct systems shall
be resealed in accordance
with NAIMA specification.
Only closure techniques which
comply with UL181 or UL181a
are suitable for fibrous
glass duct system closures.
Openings will be created
using either a ship lap tool
or the 45° angle protocol.
- The Contractor shall
insure that all motorized and
manually operated dampers and
splitter-damper positions are
marked to identify the
original position before
commencing work to assure
they are returned to the
original setting after
completion of the cleaning
process.
- All dampers needing
repair or replacement shall
be brought to the attention
of the Owner.
18.
MATERIALS,
CHEMICALS AND EQUIPMENT
- The Contractor shall use
materials, chemicals and
equipment which are specified
herein and pre-approved by the
Owner or his representative. All
sanitizers and disinfecting
agents or products with an
antimicrobial effect must be EPA
registered for the specific
application and usage.
19.
ANTI-MICROBIAL
TREATMENT, SANITIZERS & COATINGS
- Contractors must have
verification of similar projects
for applying a short term
residual antimicrobial solution
intended for use in HVAC systems
when directed and specified by
consulting building hygienists
(Oxine is a registered product
for this purpose).
- Surfaces shall have been
cleaned using source removal
processes prior to use of any
chemical sanitizer and/or coating
application. Coating will be a
long term residual EPA registered
product designed for HVAC
systems.
- Sanitizers, when used,
shall be applied per
manufacturer's instructions, and
will be used prior to coating
application. System shall be
thoroughly dried out after
application of sanitizers.
- HVAC anti-microbial
coating shall be applied
according to manufacturers
instructions. Coating shall be
sprayed directly onto interior
ductwork surface, rather than
"fogged" downstream
onto surfaces. A continuous film
must be achieved by the coating
application. Application
thickness shall meet the
manufacturer's recommendations.
- Spray fumes shall be
controlled by negative air
equipment and proper filtration
during application, exhausting
volatiles to the outside.
Negative pressure should be
maintained for at least a
two-hour period after coating
application to remove volatiles
from the system. Maximum outside
air must be brought in through
the system for at least 48 hours
after application of coating.
Note:
The porosity of the surface will
determine the square feet per gallon
coverage, which will be at a spread of
200 square feet per gallon to 400 square
feet per gallon.
20.
WORKMANSHIP
- The Contractor shall use
materials, chemicals and
equipment which are in their
original containers. No open or
used containers will be allowed.
- The cleaning process and
deposit removal shall be
accomplished by personnel skilled
and trained in the specific
discipline. The access,
preparation and dismantling of
equipment for such work shall be
performed by qualified HVAC
personnel.
- The Contractor shall
exercise special care to prevent
any damage to the equipment,
electrical motors of systems,
ceiling tiles and to the building
from water and/or chemicals
resulting from the cleaning
process. All interior equipment,
furniture, files and material
shall be adequately covered and
protected as necessary to prevent
damage. Any damaged fixtures,
equipment or systems shall be
repaired, if possible, or
replaced with equal equipment at
no cost to the Owner.
21.
RESPIRATOR
PROTECTION PROGRAM (RPP)
- Occupational Health and
Safety Administration (OSHA)
general industry standard for
respiratory protection 219 CFR
1910.134 requires that a
respirator protection program be
established. In order to perform
remediation work, an OSHA
Respiratory Protection Program
(RPP) Certificate of Completion
by each remediation employee and
an in-house RPP must be
submitted.
22.
CONTRACTORS
RESPONSIBILITIES
THE
CONTRACTOR SHALL:
- Be responsible for
unclogging HVAC components of the
herein contracted air conveyance
system including; coils, supply
registers, dampers, turning
vanes, etc., fouled by dust and
other contaminants.
- Report all damaged or
deteriorating ductwork and/or air
handler insulation to the Owner
for his inspection and decision
as to remediation.
- Authorized unsupervised
nights. A "Progress
Report" is to be faxed or
delivered to the Owner within 12
hours of work completion.
23.
IAQ/HVAC
REMEDIATION EQUIPMENT
- Minimum equipment
requirements are as follows:
- Indoor portable, HEPA
filtered negative vacuum system
at 4,000 to 6,000 CFM. HEPA
filtered vacuum shall be fitted
with minihelic gauges reading in
"inches of water gauge"
to insure proper negative
pressure is maintained, thus
preventing escape of debris
removed during the cleaning
process into the inhabited area.
- All negative vacuums
shall be HEPA filtered and shall
meet with all NADCA Standard
1992-01 equipment requirements
- Efficiency of HEPA vac
filtration to be a minimum of
99.97% at .3 microns.
- Duct brushes to vary in
size from 3" to 18" and
designed of light nylon bristles.
- Portable air compressor
rated at 150 to 200 PSI and 15 to
17 CFM.
- Pressure washer rated at
800-1500 psi.
24.
DUCT
SYSTEM REMEDIATION
- The Contractor shall
clean all components of air
conveyance system (i.e. sheet
metal ducts, rigid fiberglass
ductboard, flex duct, masonry,
etc.). Cleaning will properly
remove lint, hair, fungi, dirt
and other foreign materials and
residues.
- The cleaning procedures
shall be accompanied by the use
of specialized equipment, i.e.,
high efficiency vacuum system
utilizing HEPA filters, high
pressure washers, duct brushes
etc., as required.
- Special attention shall
be taken while cleaning to
prevent high levels of microbial
contaminants from becoming
airborne and disseminated into
occupied areas. All effluent
shall be removed and disposed of
by the Contractor.
- The Contractor shall,
during decontamination, maintain
certified respirators, safety
glasses and clothing according to
the OSHA respiratory protection
standard 29-CFR-1910.134.
- The Contractor shall be
responsible for unclogging and
thoroughly cleaning HVAC duct
system components including
reheat coils, supply registers,
dampers, VAV boxes, turning
vanes, etc., fouled by dust and
other contaminants.
- The Contractor shall
insure that all damper and
splitter-dampers are marked to
identify the original position
before commencing work. All
components will be returned to
their original setting upon
completion of the cleaning
process.
- Manually operated
dampers shall be firmly reset in
their original position after
cleaning.
- Dampers requiring repair
or replacement shall be brought
to the Owner's attention.
- DAMPER REPAIR OR
REPLACEMENT IS NOT PART
OF THIS CONTRACT, BUT IS
AVAILABLE AS AN OPTION.
- Return air ducts are to
be cleaned and decontaminated if
ducted returns are used in the
subject HVAC systems. Open
plenums above ceilings and
utility chases used for return
air purposes shall not be cleaned
unless requested and handled as
an additional work order.
- The Contractor shall
wash all terminals, grills and
diffusers with a non-toxic,
disinfecting solution.
- When requested or
specified, Contractor must be
capable, prior to reinstalling
terminals, to treat with a
long-term antimicrobial product.
25.
AIR
HANDLER REMEDIATION
- The Contractor shall
insure the supply and return fans
or blowers relating to air
handler zones of influence are
thoroughly cleaned. Areas cleaned
shall include blowers, fan
housings, blades, vanes, shaft,
baffles, and drive assemblies.
- Any surface with
contamination deposits shall be
removed in the manner previously
outlined.
- Any components or items
within the air handler units that
could possibly be subject to
damage by the cleaning process
shall be properly protected
during the cleaning process, as
applicable.
- When requested or
specified Contractor must be
capable of coating the interior
insulation, frame-work and metal
surfaces, (excluding heat
transfer components), with a long
term antimicrobial coating
product.
- The Contractor shall
remove contamination from all
cooling coils. Coils shall be
thoroughly cleaned on all
exterior surfaces, i.e., both
upstream and downstream. In the
interior coil bank, all
non-permanent impacted
contamination shall be removed in
the interior coil bank permitting
air flow and heat transfer. Coils
shall be thoroughly rinsed to
remove latent residues.
- Coils may be cleaned
with non-toxic, non-acid cleaner
if properly rinsed and flushed
after cleaning.
26.
AIR
HANDLER INSULATION
When
requested or specified Contractor must be
capable of remediating exposed degraded
insulation in air handlers and/or
ductwork requiring replacement.
REPLACEMENT OF DEGRADED INSULATION IS NOT
COVERED BY THIS CONTRACT, BUT IS
AVAILABLE AS AN OPTION.
27.
AIRSIDE
SURFACE TREATMENT (OPTIONAL)
- *AIR HANDLER(S)
- *DUCT SYSTEM(S)
- If indicated in the
detailed bid specifications, once
modifications and cleaning have
been accomplished, the Contractor
shall apply an EPA registered
antimicrobial application
designed specifically for HVAC
ducts to all airside surfaces of
the air conveyance systems(s)
selected above.
- The antimicrobial
product shall be sprayed directly
onto the airside surface of the
ductwork system. It shall not be
sprayed from a distance of more
than 30". Fumes resulting
from the antimicrobial treatment
shall be contained within the
enclosed
28.
POST
REMEDIATION IAQ TESTING (SEE 3.0)
- Bioaerosol surface
sampling to be performed by
trained personnel. Cultures shall
be quantified to identify
bacteria and fungi.
- Cultures of surface
testing to be characterized by a
Microbiologist to quantify and
qualify microbial content.
Microbial evaluations will
include bacterial and fungal
protocols.
- An Indoor Environmental
Report is to be provided with
documentation to include a report
of the HVAC systems which relates
to air handlers and ductwork.
This shall include air flow
measurements before and after
remediation, and documentation of
any deficiencies.
- Final air flow and
differential pressure readings
are to be performed by the
Contractor using manometer
equipment.
29.
WARRANTY
- Contractor is to issue
warranty on workmanship and
material for a period of one year
from completion of work.
("*"
- Optional)
(c) 1996
DUCTBUSTERS, Inc. All rights reserved.
|